TAP100 Application Software Manual
Revision 3.3 Page 69
Once communication is complete, the global lock/unlock function has been enabled.
Disable Global Lock/Unlock
The disable global lock/unlock (GLU) function disables the ability for an external device to
automatically lock or unlock all readers on the network at one time.
Disabling the GLU feature from the enabled state while a global unlock is in force will immediately
lock all doors and then restore the doors to the appropriate automatic lock/unlock (ALU) state
(see Table 2 to determine the appropriate ALU state).
Regardless of if the GLU command is enabled or disabled, every state change at the GLU input is
logged and forwarded to the host.
To disable the global lock/unlock function, use your pointing device and select Readers and then
Disable global lock/unlock. The Status Message Line will display:
Once communication is complete, the global lock/unlock function has been disabled.
Table 2 - Automatic Lock/Unlock State
ALU STATE LOCK STATE EVENT PXL-100 ACTION STATE
CHANGES
Lock Command no action
LOCKED Unlock Command unlock door SUSPEND,
UNLOCKED
Global Secure Time no action
ON
Lock Command lock door SUSPEND,
LOCKED
UNLOCKED Unlock Command no action
Global Secure Time no action
Lock Command no action
LOCKED Unlock Command unlock door
Global Secure Time no action
OFF
Lock Command lock door
UNLOCKED Unlock Command no action
Global Secure Time lock door
Lock Command no action
LOCKED Unlock Command unlock door ON, UNLOCKED
Global Secure Time ON
SUSPEND
Lock Command lock door ON, LOCKED
UNLOCKED Unlock Command no action
Global Secure Time ON
Initiating communication with local network on COM1 . . . please wait.